RUTTE Sicherungstechnik

Guides · 26 November 2026

Maintenance contracts for security systems: what should be covered

Published on · Publisher: RUTTE Sicherungstechnik GmbH

Maintenance contracts for security systems: what should be covered

A maintenance contract should set out which systems are checked at which intervals, which services are included, how faults are reported and handled, and what the documentation looks like.

Fire alarm inspection
every quarter
Fire alarm maintenance
once a year
Detector replacement
after 5 or 8 years

Which systems and services belong in the contract?

The contract should contain a list of all systems with their location and scope. Only then is it clear what is being maintained. The contract should also distinguish three services: inspection, maintenance and repair.

Define what is covered by a flat rate and what is charged by time and materials. This mainly concerns spare parts, batteries, detector replacement and call-outs after faults. Also state the times at which the systems are accessible and a contact person on site.

Which intervals need to be defined?

The intervals follow from the standard, the insurance contract and the manufacturer specifications. The contract should state them for each system:

  • Fire alarm systems: inspection every quarter at roughly equal intervals, maintenance once a year
  • Detector replacement: replace automatic point-type smoke detectors without contamination compensation after 5 years and those with contamination compensation after 8 years, or have them checked at the factory
  • Intruder alarm systems: intervals from the standard and the insurance contract, maintenance at least once a year
  • Video surveillance and access control: in line with manufacturer specifications and agreement

How are faults dealt with?

The contract should state the reporting channel, the availability and the response times. Response times are agreed case by case. They depend on the system, the location and the level of protection needed.

If the installer is to work by remote access, the access and IT security also belong in the contract. RUTTE operates a service emergency line around the clock. We set response times in the maintenance contract.

What is part of the documentation?

The documentation includes a report listing defects after every visit. It is your proof to the insurer, the authority and authorised inspectors. The entries in the log book are added to this.

Also settle who keeps software versions and configuration backups, and who updates plans and detector lists after alterations. Keep the reports in good order so that they are immediately to hand at an inspection.

What should you check before signing?

Before signing, you should check the company's qualifications and the contract terms. The operator's duties remain with you even with a maintenance contract. This article gives an overview and is no substitute for legal advice.

  • Qualifications: certification to DIN 14675 for fire alarm systems, VdS approval for intruder alarm systems with a VdS installation certificate
  • Term, renewal and termination
  • Rules on price adjustment
  • Handling of extensions and changes to the system
  • Software upkeep and updates
  • Your own tasks, for example visual checks and keeping the log book
All articles